Power Monitoring Expert - Why can't I choose an archived database to run a report on in Reporting Configuration Manager?

Issue
The user cannot select the ION_Data archive from the Reports Configuration drop down menu.

Product Line
Power Monitoring Expert (PME)

Cause
This can happen after an archived database from a previous version of Power Monitoring Expert (PME) has been upgraded because the Value for the Schema gets incorrectly set to ION_Data. When you go to Reporting Configuration Manager to select your archived database, it will not show up in the list as a database to choose.

Resolution
Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

For PME 7.x, 8.x:
First, open SQL Server Management Studio and connect to the PME instance.
Then, expand the archived database and expand the tables folder.
Next, right click on "dbo.Registry" table and select the "edit top 200 rows" option. (as shown in screen shot below)

Database selection

Next, edit a field in the Registry table in your archived database( dbo.Registry table). After upgrading your archive in PME7.2, the Value for the Schema in the Registry table will say 'ION_Data'.

Schema table


User will need to edit the Value from "ION_Data"  to  "ION_Data_Archive" as shown below. Once that is done, your archived database will show up in Reporting Configuration Manager and you will be able to use this database in Reports.Schema table 2

For PME versions 9.0 & greater:

  1. Upgrade the archived database by navigating to Management Console > Tools > Database Manager > right-click the archived database > left-click Upgrade Database... > confirm the database and left-click OK > wait for the script to finish executing.database manager
  2. Open SQL Server Management Studio and connect to the PME instance.
  3. Expand the archived database and expand the tables folder.
  4. Right-click on "dbo.Registry" table and select the "Edit Top 200 Rows" option. (as shown in screen shot below)
    dbo.registry edit top 200 rows
  5. Edit the Value "ION_Data" to "ION_Data_Archive" as shown below. SSMS fields to edit
  6. After completing the above steps, navigate to Management Console > Tools > Reports Configuration > Reports and you should be able to select the archived database.

reports configuration

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings