WebReach Historical Graphing Cannot Complete Because Data Is Missing

Goals and Symptoms

The following article describes an issue where WebReach cannot graph historical data and returns an error message stating that the data is missing. This problem is the result of a security setting that tells Internet Explorer to silently reject cookies sent by 3rd part sites. This issue can be corrected by modifying 3 default WebReach .asp scripts.

Facts and Changes

Keywords

WebReach

ASP

Internet Explorer

P3P Compact Policy

Causes and Fixes

Adding a P3P Compact Policy to WebReach:

  • 1. Open DisplayGraph.asp in Notepad. Add <% Response.AddHeader "P3P","CP=CAO PSA OUR" %> above the <html> tag. Save and close the file.
    2. Open DisplayXMLData.asp in Notepad. Add Response.AddHeader "P3P","CP=CAO PSA OUR" below the "Option Explicit" command. Save and close the file.
    3. Open GetLogs.asp in Notepad. Add <% Response.AddHeader "P3P","CP=CAO PSA OUR" %> above the <html> tag. Save and close the file.

More Information

See Microsoft Knowledge Base Article #323752

Original article#10917


Legacy KB System (APS) Data: RESL182944 V1.0, Originally authored by DaMi on 03/20/2007, Last Edited by DaMi on 03/20/2007
Related ranges: ION Enterprise

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings