我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to Accuracy Test the ION 6200 Based on Digital Outputs

Issue

How to accuracy test the ION 6200 based on digital outputs?

Product Line

ION6200 Series

Environment

ION6200 Energy Meter – Accuracy Testing Using Digital Outputs

Resolution

Follow this procedure to test the kWh accuracy of the ION 6200:

  1. Acquire a kWh test set (e.g., Rotek brand).
  2. Wire the meter according to the test set instructions.
  3. Power up the ION 6200 (for maximum accuracy, wait until the unit reaches its operating temperature of approximately 41 °C).
  4. Use Digital Output 1 (DO1), which by default is configured for kWh pulsing at 1.0 Wh per pulse.
  5. Run the test and compare the DO pulse count to the Wh count on the test set.
  6. The result should be within the meter’s accuracy specification: ±0.5%.

Important Note:
To ensure precision, the test duration should be at least 1000 seconds (16 minutes and 40 seconds), regardless of the pulse weight (kT value). Longer test periods are recommended for higher accuracy. Ensure the kT value is low enough to generate at least two pulses during the test.

Background Information:
Unlike some other meters (e.g., ION8600) that have a calibration pulse module for near-instant pulse generation, the ION6200 generates pulses after each evaluation of the energy register on its regular 1-second processing cycle. This can introduce up to a 1-second delay, making a longer test period necessary for reliable accuracy verification.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings