Issue
For ION Enterprise: When trying to open WebReach, the user may get the error page shown below in the screen capture.

Error message

Error reads:
The page cannot be displayed
There is a problem with a program on the page you are trying to reach, and the page cannot be displayed.
HTTP 403.1 Forbidden: Execute Access Forbidden
Internet Information Service

For Power Monitoring Expert: When trying to open the Diagrams tab of the Web Applications, the user may get the error page shown below in the screen capture.

Power Monitor Expert
Error reads:
HTTP Error 403.1 - Forbidden
You have attempted to run a CGI, ISAPI, or other executable program from a directory that does not allow executables to run.

Product Line
ION Enterprise 4.5
ION Enterprise 5.x
Struxureware Power Monitoring 7.x
Power Monitoring Expert 8.x

Environment
ION Enterprise WebReach
PME WebApplications
Internet Information Services

Cause
The ION virtual directory does not have permission to execute the necessary scripts for proper operation.

Resolution
For ION Enterprise:

In IIS, go to the properties of the site, and make sure the "Execute Permissions" is set to "Scripts and Executables" and not "None".ION Properties

For Power Monitoring Expert:

In IIS, navigate to Default Web Site > ION and open the Handler Mappings. Right-click and select Edit Feature Permissions. Check "Execute".Handler mappings

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings