我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Webreach navigation problems in Internet Explorer

Goals and Symptoms

When browsing the diagram with Webreach, for some reasons parts of the diagram don't work. Sometimes the historical logs don't show up. The same diagram seen from Vista works fine.

Facts and Changes

Webreach, browser, navigation

Causes and Fixes

The cause for this issue is that the IIS (Internet Information Services) has difficulties accessing the hierarchy of the different diagrams. Hence it is possible that during the session, the browser is lost and some links appear to be missing, or some queries don't execute properly. To avoid this issue, there are two possible workarounds:

  • Refrain from using the "Back" button in Internet Explorer. Using the back button uses the content of the cache file on the client, and doesn't make a new query to the IIS. Use the "Back to network diagram" button instead.
  • Make sure all the Objects or Datalog Viewers in Vista are set as "Custom Link" or "Custom Query Server" instead of "Inherit from parent window". When browsing the diagrams, the "Inherit..." option can cause the IIS to get lost.





Last Revised: November 19, 2007
Applies To: ION Enterprise, Webreach
Public
All content © 1992-2007 Schneider Electric

Legacy KB System (APS) Data: RESL189301 V1.0, Originally authored by KBAdPM on 11/20/2007, Last Edited by KBAdPM on 11/20/2007
Related ranges: ION Enterprise V5.6, ION Enterprise V5.5, ION Enterprise V5.0

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings