我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Will PME retain historical data if a meter is deleted and then added again later with the same name

Issue

User would like to keep the historical data of a certain device but needs to make a change that requires the device to be removed from the PME system.

Product Line

Power Monitoring Expert 2024

Power Monitoring Expert 2023

Power Monitoring Expert 2022

Power Monitoring Expert 2021

Power Monitoring Expert 9.x

Power Monitoring Expert 8.x

Power Monitoring Expert 7.2.x

Environment

PME Databases

Management Console

Cause

User needs to remove and readd a unit from their PME system, such as for changing out the device connection type from serial to direct ethernet or some other reason but would like to ensure that their historical data remains.

Resolution

As long as the node/source name remain the same, the historical data will remain intact since ION_Network and ION_Data reference logged data to the node name. If a device/node is deleted from Management Console, and a new device with the same name is created, ION_Data will continue to log the new data on top of the existing data from the original source name.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings