How to Modify the Meter Configuration Report in ION Setup?

Issue:
You can modify and choose to show less or more information about the meter's configuration.

Product Line:
ION Setup 3.0

Environment:
ION Setup 3.0

Cause:
The Meter Configuration Report in ION Setup is useful to find out various settings in ION Setup. The report has predetermined parameters.
An example excerpt from a Meter Configuration Report is shown below:

Meter configuration report


Resolution:
There is a line in the QuickIon.cfg file which can be modified to display more or less information about the meter's configuration.

The QuickIon.cfg file is specific for each meter type and can be found using Windows Explorer at the Program Directory for ION Setup.

1) Tools>Options

Ion Setup - Tools


2) Navigate the to the Program Directory ...ION Setup\Tables\

Options

3) Open the folder for the Meter type and Display


Feature Set

4) Open the QuickIon.cfg file in a text editor such as Notepad.

The PrintList line in the QuickIon.cfg file is near the top and looks like the following:

PrintList=0,7,1,31,0,1,3,3,31,0,15,1,3,127,7,1,1,1

The numbers following the PrintList command define which screens and tabs in the Setup Assistant that will be copied into the Configuration Report.

Each number corresponds to an Assistant#, starting from Assistant1=Template, Assistant2=Basic Setup and so on... (these are defined in the QuickIon.cfg file itself)

Understanding the Syntax
  1. Convert the decimal number to binary format.

    7=111  (format=Bit3Bit2Bit1)
  2. Parse this binary number out to know which Tabs for that Screen will get printed.

    Bit1 (LSB) = 1 means that Tab1 will get printed.
    Bit2 = 1 means that Tab 2 will get printed.
    Bit3 = 1 means that Tab 3 will get printed.
    etc...

    0 would mean that no tabs get printed for this screen.

Example
Display the fourth tab (Register Edit) in the first screen (Template)

Binary: 1000
Decimal: 8
New PrintList line:
PrintList=8,7,1,31,0,1,3,3,31,0,15,1,3,127,7,1,1,1

New Meter Configuration Report:

Meter configuration report

NOTE: Sometimes the QuickIon.cfg from the Version 2.0 Default folder will need to be changed, instead of the file from the specific Feature Set A folder

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings