Multiple node query works in ION Enterprise Vista but not in Webreach.

Goals and Symptoms

Webreach functionality works for everything except multiple node queries. Webreach gives the following error:

MultipleNodeQuery

Microsoft OLE DB Provider for SQL Servererror '80040c8e'

Error with provideHTML. Error with GenerateHTML. WebReachHistoricalASP in GetQuery: -2147218290 Cannot execute default connection: An error occurred in Execute: 'PML' is not a recognized ODBC vendor clause option.

/ION/Historical/GetLogs.asp, line 51

Causes and Fixes

In ION Enterprise Vista right click on the data viewer experiencing the issue with the toolbox open and go to the Query tab. Choose edit query here. After the screen where the nodes are chosen and the screen to choose the logs appears for each node as shown below.

Check the Advanced log view box shown in the red box above. Choose Finish, ok, and save the Vista diagram. Open up a new webreach screen and the problem should be resolved.

Attachments

(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/d4de634171ece0f0c12575ae001099a2/fl_block_5/0.1AD6?OpenElement&FieldElemFormat=gif)
Date Created: October 29, 2008
Last Revised: May 5, 2009
Public
Original Author: MN
All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL198436 V1.0, Originally authored by MiNe on 05/06/2009, Last Edited by MiNe on 05/06/2009
Related ranges: ION Enterprise V5.5, ION Enterprise V5.6

施耐德電機Taiwan

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings