How To Log Visits to an ION Enterprise WebReach Site

Issue

Show a detailed log of WebReach site visitors for an ION Enterprise WebReach deployment.

Product Line

ION Enterprise (WebReach)
PME
Note: WebReach was replaced by Web Applications for PME 9.0 and newer.

Environment

Internet Information Services (IIS)

Cause

Auditing or troubleshooting requires a visitor/access log (IP, user agent, timestamps, status codes) for the WebReach site. IIS logging provides this information.

Resolution

Perform all actions with appropriate server change controls. No references inside this section (per your guideline).

Enable logging on the WebReach virtual directory (IIS)
a. Open Control Panel → Administrative Tools → Internet Information Services (IIS) Manager.
b. In the Connections tree, expand ServerName → Web Sites → Default Web Site → ION (the WebReach virtual root). Right‑click ION → Properties.
c. On the Virtual Directory tab, check Log visits.

ION properties

2. Locate the site log settings and file path
a. In IIS, right‑click the parent of the ION virtual directory (typically Default Web Site) → Properties.
b. On the Web Site tab, ensure Enable logging is selected, then click Properties to view the log file directory and format.

Web site properties

*This will show the location of the log file. You can change the location by clicking the Browse button.

Logging properties

3. Read the log file: Navigate to the path shown in Step 2 (e.g., the site’s W3C log directory), then open the relevant W3C log file to review visitor entries (date, time, client IP, method, URI, status, user agent, etc.).

Notepad

Recommendation:

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support information

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings