Energy Pulsing cannot be setup on the E5600 via the Optical Probe

Issue:

When connecting to an E5600 meter for the first time, energy pulsing cannot be properly enabled when configuring the meter through the optical port only.

Product Line:

E5600 meter

Environment:

ION Setup
Optical probe
Modbus communication

Cause:

Although KY Relay #1 and KY Relay #2 can be enabled and KT/KE values configured through the optical port, the meter will not generate pulses until meter pulsing is explicitly enabled via the Modbus interface.

When connected through Modbus, the same configuration screen indicates that the meter is ready to pulse through its digital output, but the internal pulsing enable flag is not set by optical configuration alone.

Resolution:

If meter pulsing is configured via the optical probe and no pulses are observed at the digital output, complete the following steps:

  1. Communicate to the meter using Modbus (for example, via ION Setup).
  2. Navigate to the KY Relay configuration.
  3. Enable KY Relay #1 and KY Relay #2, then click Send to apply the settings.
  4. Confirm that a valid KE value is selected.
  5. Verify that the digital output now generates pulses.

After pulsing has been enabled through Modbus, the meter will correctly generate energy pulses on the configured digital output.

wwwwwww

Note: E5600 Meter is obsolete and the end of commercialization was 2015, click the following link for more information: E5600 Meter Obsolescence (obsolete) End of Commercialization

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings