我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Non Zero Voltage Readings on ION6200 or Siemens Access 9200 Meters when nothing is connected to the meter's voltage inputs.

Goals and Symptoms

Problem:
ION6200 or Siemens Access 9200 meters with the P24 low DC voltage power supply option will, in some cases, show readings of 1.5 - to 3.0 volts (Voltage Line to Neutral) for all phases, when nothing is connected to the voltage inputs.

Confirming the Problem:
If the ground cable is removed from the power supply module the line to neutral voltage reading returns to the correct reading of 0 Volts. Alternatively if you remove the Earth cable from the voltage input terminals the voltage reading returns to the correct reading of 0 Volts.

Causes and Fixes

Solution:
ION6200 or Siemens Access 9200 meters with P24 low DC voltage power supplies will be shipped with ferrites that will cover and attach to the power supply cable. All ION6200 or Siemens Access 9200 meters with P24 power supplies shipped after May 14, 2010 will include the ferrite and installation instructions. The ferrite information that we are using can be found below:

Ferrite Information:
Laird technologies
Steward
28A2024-0A2

Please note:
As suggested on page 11 of the ION6200 installation guide: Connect the power supply G (ground) terminal to the same point as the meter earth ground terminal.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings