Can a Micrologic trip unit communicate with 2 wire communications wiring?

Product Line
Masterpact (NT and NW) and larger frame size Powerpact (P and R Frame) and Compact NS Circuit Breakers
Trip Unit Versions

Trip UnitTrip FunctionType
2.0A (IEC Only)LSOStandard
3.0ALI
5.0ALSI
6.0ALSIG
5.0PLSIPower
6.0PLSIG
5.0HLSIHarmonics
6.0HLSIG

Environment
Communication applications using Micrologic trip units in 2 wire configurations

Cause

Older version of the breaker communication module (BCM) are not capable of 2 wire communication. The replacement, BCM ULP version, is capable of 2 wire communication

Resolution
The Micrologic trip unit must have a breaker communications module (BCM) with gray terminals. If the device has green terminals on the BCM, it is not capable of the 2 wire communications configuration, 4 wire only. Below the figures show the two units.

BCM terminal blocks
There are three possible wiring configuration for a BCM ULP, 4 Wire, 2 Wire, and 2 Wire + ULP. See the figure below for the wiring diagram for each configuration. As you see from the diagrams, the 4 wire and 2 wire configurations have the same setting on the trip unit, 4 Wire. The BCM can auto detect the correct setting.  The 2 Wire + ULP setting provides two terminals for 2-wire Modbus communication and 2 terminals for ULP protocol. ULP is a protocol common to many Schneider devices including Micrologic trip units and FDM121 display is diagram.

pin outs
The 2 Wire + ULP is the default setting on the BCM ULP. The configuration can be set using the EcoStruxure Power Commission Software , see the link below. The Micrologic A trip unit must be set using this program.  P and H type trip units can be configured from the front panel using the procedure below. See the instruction bulletins for more information.

  1. Press the Wrench button
  2. Select the Com. Setup
  3. Select Communication Parameter
  4. Select 4 wire or 2W + ULP

Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0P and 6.0P Trip Units, see 48049-137-05
Powerpact P, R, and Masterpact NW, NT Micrologic™ 5.0H and 6.0H Trip Units, see 48049-330-03

Link to EcoStruxure Power Commission Software.
https://www.se.com/us/en/download/document/Ecoreach_Installer/

Notes:

  • Powerpact H, J, and L and Compact NSX breaker use different communication hardware (IFM, NSX cord, and BSCM). The breakers use 2 wire configuration only.
  • If the BCM date code is 11351 to 12132, the user may see ComLoss errors in SMS. The user must either be running SMS 4.3 with the Micrologic patch or replace the BCM with date code 12132 or higher.
  • The Micrologic trip unit must be type P or H with date code 11351 or higher.
  • If a Cradle Communication Module (CCM) is use, it must have the new firmware to operate with 2 wire + ULP.  The CCM with the new firmware is Brand Schneider Electric and the CCM with the old firmware is brand Merlin Gerin.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings