How do I reset a TCSESM ConneXium Ethernet Managed Switch to factory default settings using Hyper Terminal?

Issue

How can a TCSESM ConneXium Ethernet Managed Switch be reset to its factory default configuration using a serial connection?

Important: Resetting the switch to factory defaults erases the existing configuration.

Product Line

  • TCSESM ConneXium Ethernet Managed Switch

Environment

The procedure described here uses:

  • 490NTRJ11 serial external management cable
  • PC with a serial COM port
  • HyperTerminal
  • Serial communication settings:
    • Baud rate: 9600
    • Data bits: 8
    • Parity: None
    • Stop bits: 1
    • Flow control: None

Resolution

  1. Connect the PC to the TCSESM switch using the 490NTRJ11 serial external management cable.

  2. Start HyperTerminal.

windows hyper terminal

  1. Create a new connection and select the COM port connected to the switch.

new connectionCOM selection

  1. Configure the COM port as follows:

    • 9600 baud
    • 8 data bits
    • No parity
    • 1 stop bit
    • No flow control
    COM properties
  2. Power-cycle the TCSESM switch.
  3. During startup, wait for the following message:

    "Press <1> to enter System Monitor 1..."

reboot TCSESM hyperterminal

  1. Press 1 within approximately 2 seconds.

    If the System Monitor is not entered, power-cycle the switch and repeat the procedure.

  2. From the System Monitor menu, press 5 to select:

    Erase main configuration file

  3. When prompted to press RETURN to delete the configuration or ESC to cancel, press RETURN.

SysMon Hyperterminal

  1. Wait for confirmation that the main configuration file has been deleted, then press any key to continue.

Reset configuration, TCSESM

  1. From the System Monitor menu, press 4 to select:

    End (reset and reboot)

reboot , TCSESM

  1. During the subsequent restart, do not press 1 when the following message appears:

    "Press <1> to enter System Monitor 1..."

back to factory, TCSESM

  1. Allow the switch to complete its normal startup.
The switch should then start with its factory default configuration.

TCSESM with default configuration

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings