我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to link a Vista Numeric or Control object to a Setup Register

Issue
On occasion there is need to view or even change configuration of a module from the Vista diagram instead of opening Designer or ION Setup.
An example would be, but not limited to, sag/ swell thresholds for power quality events.

Product Line
ION Enterprise, Struxureware Power Monitoring, Power Monitoring Expert

Environment
Vista

Cause
By default when attempting to edit a Numeric object in Vista, only Output Registers are available.  For Control objects most managers will show no compatible registers on a normal click opening.


Example of a standard Control object Edit Link

Resolution
It is possible to see the Setup Registers in the 'Edit Link' dialog in either a Numeric object or a Control object.
Use the below method to access Setup Registers for a Numeric object when the desire is view only.  This can provide a quick view of trigger setpoints for power quality, overvoltage, etc.
This method can also be used on a Control object when the desire is to make modifications to setpoints on the fly from Vista diagrams.

1.)  Right-click on the diagram object
2.)  Hold down the CTRL key then click on 'Edit Link' (note the third column is now titled Setup Registers)
3.)  Select the required register
4.)  Click Ok until the edit object is been completely exit
5.)  Save Diagram


施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings