我们今天能为您提供什么帮助?

How to convert a live database to an archive database?

Issue
How to convert a live database to an archive database.

Product

Power Monitoring Expert



Environment
SQL Server

Cause
Need to convert the live database to an archive.

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*


For instructions on creating a new ION_Data database, see FA270626 - How to create a new ION_Data Database.

Instructions below can be used to have the old ION_Data database behave as an archive
1) Open SQL Enterprise Manager (SQL Server Management Studio)
2) Open the tree hierarchy on the left hand pane of Enterprise Manager until you see the ION_Data_Archive database under the Databases folder
3) Open the ION_Data_Archive Tables
4) Right-click on the Registry table in the right-hand pane and select 'Edit Top 200 Rows'
5) Find the cell under the Value column that says 'ION_Data'
6) Click inside that cell and edit the text to say 'ION_Data_Archive' (case sensitive) and hit Enter
7) Close SQL Enterprise Manager

If the above sequence of steps do not work, use the following query.
1) Open SQL Enterprise Manager (SQL Server Management Studio)
2) Open a new query window by clicking file > new query.
3) Enter the following query below:

Warning: Make sure that the correct ION_Data_Archive database is selected or inputted into the query correctly.
Use the following SQL statement to properly update the database and set it to an archive, in the query below, ION_Data_Archive_2015, is being updated.
USE  [ION_Data_Archive_2015]
UPDATE Registry SET Value='ION_Data_Archive'
WHERE Name='Schema'

4) Open the tree hierarchy on the left hand pane of Enterprise Manager until you see the ION_Data_Archive database under the Databases folder
5) Open the ION_Data_Archive Tables
6) Right-click on the Registry table in the right-hand pane and select 'Edit Top 200 Rows'
7) Find the cell under the Value column that says 'ION_Data_Archive' to confirm the changes.
8) Close SQL Enterprise Manager

** see attachment containing the SQL script text

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support Information

施耐德電機Taiwan

附件

探索更多

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。