What does the message - Circuit Trip - mean on a Sepam Relay Series 20/40/80?

Goals and Symptoms

What does the message - Circuit Trip - mean on a Sepam Relay Series 20/40/80?

Causes and Fixes

The Circuit Trip is related to the CB control features. It indicates that the Input I11 or input I12 on Sepam is not receiving a signal. If you are not using a Circuit Breaker control the recommendation is not to use this function.

**************************