我们今天能为您提供什么帮助?
M340 Troubleshooting Guide
Goals and Symptoms
How to interpret the front panel lights when diagnosing problems with the M340.
Causes and Fixes
Modicon M340 Processor Troubleshooting
The Modicon M340 Programmable Automation Controller is a Mid-range automation system providing small size, yet powerful 32-bit processor for demanding OEM machine and industrial process applications. It is programmed using our cross-platform IEC 61131-3 application development software, Unity Pro (v3.0 or higher). The front panel has a series of LEDs that indicate the status of the M340 processor, SD Memory Card, and system communications.The Modicon M340 is available in the following models.
M340 Processors
BMXP341000 Standard Level 1, 2MB RAM, USB port,-
-
-
-
-
- 1-communication port: ModBus/Serial, includes 8MB memory card
-
-
-
-
-
-
-
- 1 USB Port for programming
1 slot for a memory SD-card
1 communication port: serial link
Shipped with 1 standard memory SD-card
- 1 USB Port for programming
-
-
BMXP342010 Advanced Level 2, 4MB RAM, USB port,-
-
-
-
-
- 2-communication ports: ModBus/Serial and CANopen master includes 8MB memory card.
-
-
-
-
BMXP342020 Advanced Level 2, 4MB RAM, USB port,-
-
-
-
-
- 2-communication ports: ModBus/Serial and Ethernet-ModBus/TCP, includes 8MB memory card
-
-
-
-
BMXP342030 Advanced Level 2, 4MB RAM, USB port,-
-
-
-
-
- 2-communication ports: Ethernet-ModBus/TCP and CANopen master includes 8MB memory card.
-
-
-
-
Processor Status Displays
Introduction
There are several LEDs available on the front panel of each processor, enabling
rapid diagnosis of the PLC status.These LEDs provide information on:
· PLC functional status
· The memory card status
· Communication with the I/O modules
· Modbus Serial communication
· Communication on the CANopen network
· Communication on the Ethernet networkIllustration
The following diagrams shows the physical location of the LEDs on the front panel of the BMX P34 processors:
BMX P34 1000/2000 Processors LEDs
Table 1 M340 Processor Status and Error indicator display
Display differences between version 1 and version 2 of the
BMX P34 20x0x module.
Searching for Errors Using the Processor Status LEDs
General
The status LEDs located on the processor inform the user of the PLCs operating
mode and any possible errors.
The errors detected by the PLC concern:
· circuits which constitute the PLC and/or its modules: internal errors
· the process driven by the PLC or the process wiring: external errors
· functioning of the application executed by the PLC: internal or external errorsError Detection
Error detection is performed at startup (autotest) or during operation (which is the
case for most equipment errors), during exchanges with the modules, or during
execution of a program instruction.
Certain "serious" errors require the PLC to be restarted while others are left to the
user to decide how to proceed depending on the level of application required.
There are three types of error:
· non-blocking
· blocking
· processor or systemBlocking Errors
General
Blocking errors, caused by the application program, do not cause system errors but
prohibit execution of the program. When such an error occurs, the PLC stops
immediately and goes into HALT mode (all tasks are stopped on the current
instruction). The ERR LED flashes.
Restarting of the Application After a Blocking Error
To end this status it is necessary to init the PLC or to set the %S0 bit to 1.
The application is then in an initial state:
· The data resumes its initial value.
· Tasks are stopped at end of cycle.
· The input image is refreshed.
· Outputs are controlled in fallback position.
·
The RUN command then allows the application to be restarted.
Blocking Error Diagnosis
Indication of a blocking error is signaled by the ERR and RUN LEDs flashing on the
processor front panel.
The system words %SW126 and %SW127 indicate the address of the instruction
which caused the blocking error.
The nature of the error is indicated by the system word %SW125.
The following table presents the errors signaled by the values of the system word
%SW125.
M340 Diagnostic information Memory card
Memory Card Description
Only Schneider memory cards are compatible with BMX P34 processors.
Schneider memory cards use Flash technology and do not require a battery. These
cards can support about 100,000 write/delete cycles (typical).The Memory card access LED is located behind the Memory Card Protective Cover.
CANopen Diagnostics
BMX NOM 0200 Module Status Display
LED Indications
BMX NOE 01x0 Module
Ethernet LED
Display differences between Version 1 and version 2 of the BMX NOE 01x0 module.-
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
發佈於: 施耐德電機Taiwan