我们今天能为您提供什么帮助?
In Vijeo Designer, are there any traceable way to determine who has logged in or a variable has been changed?
Issue:
In Vijeo Designer, are there any traceable way to determine who has logged in or a variable has been changed?
Product Line:
Vijeo Designer, Magelis, Harmony
Resolution:
Yes, this feature is available and it is called System Event Group. It records system events with predefined event messages. To record variables changes, the option "Log User Operation on Variable" of the variable property must be checked. Logged variables are recorded automatically. You can view the messages on a Event Summary Object.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
發佈於: 施耐德電機Taiwan