What are the considerations for running a motor lead longer than a 100 feet on the ATS softstarters?

Issue:
Considerations for running a motor longer than a 100 feet on the ATS soft starters

Product Line:
ATS01, ATS22, ATS480, ATS48

Resolution:
Very long motor cables cause voltage drops due to the resistance of the cable.  If the voltage drop is significant, it could affect the current consumption and the available torque.
This Criteria must be taken into account when selecting the motor and the soft starter.

Ref manual 8636CT0201