我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: How can I increase the starting torque on the ATS22?
Issue:
Is there a way to adjust the torque to get the motor moving from a start position?

Product line:
Altistart 22, ATS22

Environment:
All models, all serial numbers

Cause:
The default settings in the ATS22 cannot produce enough torque to ramp up the Soft Starter, which could lead to overcurrent, overload or excessive starting time faults.

Resolution:
Increasing the parameters below can aid in providing more breakaway torque to get the motor moving and up to speed.

SET Menu:
Parameter T90 - Initial Voltage.  This value is adjustable from 10% to 50% of the full voltage, in increments of 5%.  Factory setting is 30%.
Parameter ILt - Current limit.  This is the maximum current allowed during the startup.  It is adjustable up to 700% of the Motor Rated Current (In parameter).  The maximum value is 350% of the Soft Starter rated current (IcL parameter).  Factory setting is 350%.



ADJ Menu: (To access the ADJ menu, LAC parameter under the SET menu must be set to "on")
Parameter bSt - Boost Time.  This provides an 80% pulse of the Line voltage (UIn parameter) for 0.0 to 1.0 seconds.  Factory setting is 0.0.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings