我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: How do I change the Alarm sound in Power Monitoring Expert?
Issue
A user would like to change the Alarm sound in Power Monitoring Expert.

Product Line
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020

Environment
Power Monitoring Expert Web Applications

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).*

In PME 7.2.x, 8.x, and 9.0 the AlarmSound.mp3 file can be found in:

\\Power Monitoring Expert\Applications\ApplicationFramework\ClientBin\Applications\AlarmViewer\Assets

In PME 2020 the AlarmSound.mp3 file can be found in:

\\Power Monitoring Expert\applications\SystemDataService\Content\Applications\Alarms\Content\Media

Replace this file with a desired .mp3 and rename it to AlarmSound.mp3.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings