我们今天能为您提供什么帮助?
Does the ATS22 have an analog output?
Issue:
Looking for a analog output on an ATS22.
Product Line:
Altistart 22 ATS22
Resolution:
No, there is not an analog output feature on the ATS22.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
發佈於: 施耐德電機Taiwan