Can an Altivar 12 (ATV12) Drive Be Controlled from Both the Remote Display and the Terminal Inputs?

Resolution:

Yes. The Altivar 12 can be configured to accept run commands from both the remote display and a terminal input.

Configure the following parameters:

  • ConF → FULL → CtL → FR1 = LCC
  • ConF → FULL → CON → FLO = LIH

With this configuration:

  • The drive can be started from the remote display using the RUN button.
  • The drive can also receive a run command when the contact connected to LI1 is closed.

This setup allows control from the remote keypad while maintaining an external run command through the terminal input.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.