我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What can cause an OLF or overload fault on the ATV61 and ATV71 drives?

Issue:
Overload fault on the ATV61/ATV71 drives.

Product Line:
Altivar ATV61 and ATV71 drives.

Environment:
All

Cause:
Motor is pulling to many amps and drive is tripping out on OLF fault.

Resolution:
OLF= Overload fault this fault is triggered by excessive motor current.
Check your Motor thermal setting in the Simply Start menu and make sure it equals the motor FLA rating on the motor's nameplate.
Check your load.  Run the motor and using the monitoring menu 1.2 check to see what the LCR motor parameter is displaying.  If the motor is pulling to many amps you will need to check to see what is causing your motor to overload.

施耐德電機Taiwan

附件
atv61_programming_manual_en_1760649_08.pdf [4.35 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings