SoMachine v3.1 application prompts that the 3S CanOpen Stack library is out of date. How do I resolve that issue?

Issue

When I build a Somachine v3.1 application it prompted me that the 3S CanOpen Stack library is out of date.  How do I resolve that issue?
Product Line
SoMachine v3.1, LMC058, LMC078, M238, M241, M251, M258, XBTGC, HMISCU
Environment
PLC Configuration Software for Windows
Cause
It is likely that an update of the application file has rendered the CANopenStack Library in the project older than the required version for the compiler.
Resolution

In order to get rid of the build error, you have to restore the proper version of the CANopenStack Library again. A backup copy of this library has been stored on the PC during installation of SoMachine. Please follow the following steps to get the correct library restored:

(1) Start a SoMachine session and open the project that shows up the build error

(2) Select the Library Repository function from the Tools main menu entry

(3) Select the “3S CANopenStack” library version 3.4.1.70 and uninstall the wrong library.

(4) In a next step install the correct library version. Press the Install… button in the Library Repository dialog, select the backup copy of the library, which is available in folder :

\Program Files\Schneider Electric\SoMachine\Support\

If you are running Windows 7/10 64bit, then the path would be: \Program Files (x86)\Schneider Electric\SoMachine\Support\

(5) Close the current project and reopen it again. This ensures that the new CANopenStack library is taken into account.

(6) When running another compilation of the project, the error message that was previously displayed, should no longer be valid

(7) Note that the restored library will not appear with a different revision then the old library.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings