我们今天能为您提供什么帮助?

Power Monitoring Expert - Alarms and Events not updating on remote Web Clients

Issue:

The Alarms Tab in the PME Web Applications is not updating with new Alarms and Events. The Updating indicator continues to operate which suggests the Alarms Tab is updating, but nothing new is displayed.
Product Line:

Struxureware Power Monitoring 7.0(SPM)

Power Monitoring Expert 7.2.x

Power Monitoring Expert 8.x

Power Monitoring Expert 9.0

Power Monitoring Expert 2020

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment:
Web Applications
Alarm Tab
Cause:
The Web Clients do not dynamically reconnect to the server if there is a connection loss between the remote machine and the Primary Server. If the Primary Server is rebooted or the services restarted, the Web Clients will lose connection and will not reconnect.
Resolution:
If the Primary Server is rebooted or the ION Services are restarted, all Web Clients will need to be logged out and logged back in to resume normal operation.

施耐德電機Taiwan

探索更多

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。