我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to measure the performance of a daisy chain?
Issue
Poor performance.

Product Line
Power Monitoring Expert (PME)
Struxureware Power Monitoring (SPM)
ION Enterprise

Environment
Diagnostics Viewer

Cause
Having too many devices on the daisy chain or any one of the devices is having intermittent communication.  As a result the daisy chain becomes saturated.

Resolution
  1. In Management Console, ensure that all of the devices on the daisy chain to be tested are activated.
  2. Apply the desired test load to the devices on the daisy chain (for example VIP, Vista, OPC, Diagrams, Tables, or Log Inserter).
  3. In the Diagnostics Viewer, drill down into the Communications Diagnostics and select the site of the associated daisy chain.
  4. Select the Communication Status tab.
  5. Make note of the time, right-click in the Communication Status panel, and select Reset.
  6. Let the system gather metrics. For real-time data loads, a few minutes is usually enough.  For logging, it is better to leave it for an hour, depending on logging intervals.
  7. Make note of the value in the Util (%) column. A value at or near 100% indicates that the daisy chain is saturated and it most likely exhibits poor performance.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings