我们今天能为您提供什么帮助?
PME Adding additional digits of precision to web reports
Issue
System Manger Software(SMS) has 3 digits of resolution in their web reports. After migrate to PME, most of the reports provide two digits of resolution.
Product Line
Power Monitoring Expert 7.2
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Web Reporter in PME
Cause
The reports in PME are designed to have two digits of resolution.
Resolution
- Navigate to the folder where PME/SPM is installed(as shown in the below example):
C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\web\ReportDepot\ION Reports\ION Report Packs\Default Reports
- You will see RDL files for each report in that report pack. Open up the .RDL file in Notepad.
- Replace <Format>N2</Format> with <Format>N3</Format>
- Save the file.
發佈於: 施耐德電機Taiwan