How do I load an SoMachine V4.1 application to a M241 controller via an SD card?
1. Compile your project to make sure there is no error in the project.

2. In MyController--> PLC settings set the Starting Mode to "Start in Run".

3. Rebuid your project.

4. Go to Project Option and select Mass Storage.

5. In Mass Storage window click on Macros Button and select the option Download App. This will insert three script in Download action.
6. Again click on add new in Mass Storage to insert a new action.

7. Select this new action and from command drop down select the option Reboot. This will insert a new line in script as Reboot.

8. Make sure that your drive is formatted as FAT 32 format.

9. Click on Generate Button and give the path of the drive.

10. In Message window you will see the message as a Script was generated successfully.

11. Safely remove the drive from your system and insert it into the PLC, then power on the PLC.

12. You will notice that (SD/USB) LED will start blinking. This indicate that Program Transfer is in progress.

13. At the end you will notice indication that the transfer finished successfully (M258/LMC058 - USB LED becomes solid ON, M241/M251 - SD Card is Steady ON and ERR LED is flashing)

14. Do not power off the controller but remove the drive from PLC. This automatically execute an reboot command and you can notice the reboot action of PLC.

15. After successful reboot controller will remain in Stop Mode.

16. To Start the controller simply Power off the controller and power on again. This action will put controller in Run Mode as we have selected the option Start in Run for Start Mode.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings