How do I clone an M221 controller application using an SD card?

Issue:
What are the steps to take to clone a M221 on a SD card?

Product line:
M221

Environment:
EcoStruxure Machine Expert Basic (formerly SoMachine Basic).

Resolution:
Cloning allows you to automatically back up the application, firmware, and post configuration (if it exists) of the Modicon M221 Logic Controller to the SD card.
The SD card can then be used to later restore the firmware, application, and post configuration (if it exists) to the logic controller, or copy them to another logic controller with the same reference.
Before cloning a controller, the M221 Logic Controller verifies whether the application is copy-protected or not.

NOTE:

  • The SD card must be empty and correctly formatted to perform this procedure.
  • The SD card name must be different from DATA, refer to Data Logging.
  • The detected error log and data memory are not cloned.
  • If the application is password-protected, the clone operation is blocked (the SD LED is flashing).



Creating a Clone SD Card from an existing M221 PLC:
This procedure describes how to copy the application, firmware, and post configuration (if it exists) from the controller to an SD card:
1) Format an SD card on a PC (with FAT32 file system)

2) Insert the SD card into the controller.
Result: The clone operation starts automatically and the SD LED is illuminated.

3) Wait until the end of the operation (until the SD LED is off or flashing).
If an error is detected, the SD LED flashes and the detected error is logged in Script.log file.

NOTE: The clone operation lasts 2 or 3 minutes. The clone operation has a low priority in order to minimize impact on the user logic and communication performance of the logic controller. Depending on the amount of free time in your program, the operation may require more time to complete if the logic controller is in RUNNING state compared to the STOPPED state.

4) Remove the SD card from the controller.


Restoring or Copying from a Clone SD Card into an M221 PLC
This procedure describes how to download the application, firmware, and post configuration (if it exists) stored in the SD card to your controller
1) Remove power from the controller

2) Insert the SD Card (that was the result of a Clone procedure) into the controller

3) Restore power to the controller.
Result: The clone operation is in progress
NOTE: The SD LED is lit during the operation.

4) Wait until the end of the operation (until the SD LED is off or flashing).
If an error is detected, the SD and ERR LEDs flash and the detected error is logged in Script.log file.

5) Remove the SD card and the controller will perform a restart by itself.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings