How to install and configure Microsoft Loopback adapter

Article available in these languages: Czech

Issue
To ensure ION Site Service continue to operate properly if the network connection to the server is interrupted, it may be necessary to install and configure Microsoft Loopback adapter.


Product Line
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x

Environment
Device manager

Cause
To ensure ION Site Service continue to operate properly if the network connection to the server is interrupted, it may be necessary to install and configure Microsoft Loopback adapter.

Resolution
To install the Loopback adapter in Windows 7, Server 2008 and Server 2012 and newer OS:

  1. Click Start, then type cmd in the search box.
  2. When cmd.exe appears, right-click it and choose Run as administrator.
  3. In the command prompt, type hdwwiz.exe and press Enter.
  4. Click Next.
  5. Select Install the hardware that I manually select from a list (Advanced), then click Next.
  6. Select Network adapters, then click Next.
  7. Select Microsoft as the manufacturer, select Microsoft Loopback Adapter as the adapter (for Server 2012 and newer OS the adapter will be called Microsoft KM-Test Loopback Adaptor), then click Next.
    - If Microsoft Loopback Adapter is not install, you can get the installation here: Microsoft Loopback Adapter
  8. Select Next to confirm the installation.
  9. Select Finish to complete the installation.

To configure the newly created adapter:

  1. Click Start > Control Panel > Network Connections.
  2. Select the newly created connection (named Local Area Connection #, where # is its order number).
  3. Right-click on the selected connection and choose Properties from the menu.
  4. Confirm that Microsoft Loopback Adapter or Microsoft KM-TEST Loopback Adapter is displayed in the Connect Using: field.

  5. Deselect everything except Internet Protocol (TCP/IPv4).

Loopback

  1. Select Internet Protocol (TCP/IP), and click Properties to open Internet Protocol (TCP/IP) Properties.
  2. Select Use the following IP address. Fill in the IP address and Subnet mask fields.

    Example: 10.10.10.10, 255.255.255.0
  3. Click Advanced to open Advanced TCP/IP Settings.
  4. Switch to WINS and select Disable NetBIOS over TCP/IP.
  5. Click OK to close Advanced TCP/IP Settings.
  6. Click OK to close the Internet Protocol (TCP/IP) Properties.
  7. Click OK to close the connection properties.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings