我们今天能为您提供什么帮助?

Advance One Line Crashing with error "Password Encryption Failed - Cipher initialization failed" in the AdvanceOneLine Status log

Issue

Advance One Line crashes without displaying an error message. However, the Advance One Line Status log shows the following error: Password Encryption Failed – Cipher initialization failed

Product Line

Power SCADA Operations 8.2

Power SCADA Operations 9.0

Power Operation 2020

Power Operation 2021

Power Operation 2022

Power Operation 2023

Power Operation 2024

Environment

Starting Runtime
Advance One Line in PowerLogic SCADA

Cause

Running the Computer Configuration multiple times and repeatedly clicking Register can corrupt or invalidate the local encryption configuration used by Advance One Line.

Resolution

Solution 1 — Reset Advance One Line user configuration

  1. Navigate to: C:\ProgramData\Schneider Electric\PowerSCADA Expert\v7.40\User
  2. Open the folder corresponding to the project name in use.
  3. Open advoneline.ini with Notepad.
  4. Delete all entries except the first line.
  5. Save the file.
  6. Restart Advance One Line.

Solution 2 — Regenerate the cipher configuration

  1. Navigate to: C:\ProgramData\Schneider Electric\PowerSCADA Expert\v7.40\Config
  2. Rename PowerLogic.Cipher.dll.config to PowerLogic.Cipher_old.dll.config.
  3. Restart Advance One Line.

Renaming the PowerLogic.Cipher.dll.config file forces the system to regenerate the encryption key for the machine, resolving the cipher initialization failure.

Recommendation

If you are using an older version of Power Operation, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com

Support details







施耐德電機Taiwan

探索更多

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。