Cannot View diagrams in engineering client after running EPSS Generator tool

Issue
Diagrams created from the EPSS generator tool will not open in the engineering client; Diagrams open fine in Vista from the server.

Product Line
PMEHC 7.22
PMEDC 7.22
PME 8, 8.1, 8.2

Environment
StruxureWare Power Monitoring Expert Vista Application (7.22, 8, 8.1, & 8.2)

Cause
EPSS Generator tool does not bring the network path over for the diagrams.  Right-clicking on the link in vista will show the local server path for the diagrams "C:\Program files(X86)\Schneider Electric\Power Monitoring Expert\config\diagrams\ud\EPSS\diagram.dmg"

Resolution

1. In Vista engineering client, click "File > Open" you will see the server path to the diagrams. You can copy this or note it.

2. Right-click on the link in the engineering client and then select the action tab in the path field.

3. Remove the local path EG, "C:\Program files(X86)\Schneider Electric\Power Monitoring Expert\config\diagrams\ud\EPSS\diagram.dmg", keeping the diagram name and past the server path you copied, it will now look something like this:
"\\Powerlogic02\ION-Ent\config\diagrams\ud\EPSS\diagram.dgm"

4. You will need to do this for each link created by the generator tool.