Can ATV312 drive display RPM instead of Frequency?
Issue:
How to display the RPM on an ATV312?
Product Line:
ATV312
Environment:
All model numbers, all serial numbers
Cause:
Customer wants to display the RPM on the drive display.
Resolution:
This can be done by creating custom display parameter.
In menu SEt-, go to SdS and set it to RPM/60Hz then press enter to save it.
Go back to menu SUP and go to SPd3, press enter twice to set it.
How to display the RPM on an ATV312?
Product Line:
ATV312
Environment:
All model numbers, all serial numbers
Cause:
Customer wants to display the RPM on the drive display.
Resolution:
This can be done by creating custom display parameter.
In menu SEt-, go to SdS and set it to RPM/60Hz then press enter to save it.
Go back to menu SUP and go to SPd3, press enter twice to set it.