我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Video: What would cause the ATS48 to show RDY even with a run command?
Issue:
Troubleshooting a RDY (ready) status following a run command on the Altistart ATS48 Soft Starter by verifying supply voltages and wiring with a multi meter.

Product Line:
Altistart ATS48

Environment:
All models

Cause:
The Soft starter is stuck on RDY and will not run with a run command.

Resolution:
Confirmed that the +24V supply is still there.  Measure between 24V and COM on soft start.  If necessary remove wires off the terminals.
If in 2 wire control mode, make sure you have 24vdc on Run and Stop.
If you are doing 3 wire control make sure you have +24vdc on Stop and you are pulsing Start to get the soft starter to start.  Stop is normally closed and start is normally open push button contacts.
If you are doing NET control over a network  you will need to make sure +24vdc is supplied to the Stop input at all times.

施耐德電機Taiwan

附件
instruction bulletin enclosed ATS48.pdf [1.3 MB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings