我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How convert a 984 HSBY application to Unity
Issue
How convert a 984 HSBY application to Unity

Product Line
Unity

Environment
Windows 10

Resolution
  • Open the ProWORX 32 application.


  • Select the appropriate settings in the 'L984 Options' window.
  • Click on OK


  • The application imported without any errors.   Attempts to rebuild the application will fail with two errors:


This error is expected because the application contains a CHS loadable function block.

The reason for the error is because Unity is not able to delete the CHS loadable block.  The CHS block is not needed in a Unity
Hot Standby application.  The Hot Standby function is managed from Hot Standby window in the PLC configuration.

To resolve the issue:

  • Double click on the error message (This will open the DFB)

User-added image

  • Delete the structured text in the DFB block.

User-added image

  • Rebuild the application.
  • Save the changes.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings