Can the ION Meter calculate Total demand distortion (TDD)?

Issue

The ION meters calculate Total Harmonic Distortion (THD) by default and the user would like to calculate Total demand distortion (TDD) instead.

Product line

ION 7550/7650, PM8000, ION 8650/8600, ION7330/ION7350, ION9000

Environment
ION Setup 3.0

Resolution
Total demand distortion as defined in the IEEE 519 standard is he total root-sum-square harmonic current distortion, in percent of the maximum demand load current and can be calculated using the following formula:
tdd equation
The IL above is peak or maximum demand load current at the fundamental frequency component measured at the point of common coupling (PCC) derived from the 15 minute or 30 minute billing KVA. With the load already in the system, you can calculate IL as the average of the maximum demand current for the preceding 12 months. for a new installation, you can estimate IL by using predicted load profiles.

One can either setup the ION meter to record the maximum demand current or we can input a calculated value as following:

  1. Navigate the ION meter in advanced mode (ctrl + left click)
  2. Select the 'Maximum Modules' folder and then right click the white space to insert a new module
  3. The source of this new module should be the sliding demand current input as shown below.
    creating a maximum module and linking its input
  4. Change the output register’s name to make it easier to link later on.
  5. Now create maximum modules for I b/ I c current demand accordingly following the same process.
  6. Navigate to Harmonic Measurements Modules and link the Max Demand input each to the output of the maximum module created in step 2.
  7. Do this for each: Ia = I1, Ib = I2, and Ic = I3.
    linking the maximum module to the harmonic measurement module
  8. In the setup tab, change the display mode to “MAGNITUDE OUTPUTS DISPLAYED AS PERCENTAGES“ and the THD display mode to Percentages.

Alternatively, if the IL is to be calculated, one can input a constant using an arithmetic module as following:

  1. Navigate to arithmetic modules and insert a new module
  2. Link Source1 to I a mean from the sliding demand window modules.
  3. In the setup tab, change formula one to the constant calculated in Amps
    arithmetic module in creating the IL value
  4. Change the Output register’s name to make it easier to link.
  5. Navigate to harmonic measurements module and then link the Max Demand input to the output of the arithmetic module created created in step 2
  6. In the setup tab, change the display mode to “MAGNITUDE OUTPUTS DISPLAYED AS PERCENTAGES “ and the THD display mode to Percentages

施耐德電機Taiwan

探索更多
產品:
系列:
探索更多
產品:
系列:

需要協助?

  • 產品選型工具

    快速輕鬆地為您的應用找到合適的產品和附件。

  • 取得報價

    立即線上提交您的銷售需求,專業團隊將主動聯繫您。

  • 購買地點

    輕鬆在您所在地區找到最近的施耐德電機經銷商。

  • 支援中心

    在同一位置找到滿足您所有需求的支援資源。

  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings