我们今天能为您提供什么帮助?
What are the changes on the Micrologic trip unit performance when we install a LT Off Rating Plug?
When you use the LR off plug that means Ir = 1 and Tr = very far from standard times delay (near infinity).
There is a direct relationship between load shedding and the long time delay protection so for this reason the load shedding will remain off too.
You can replace it with the 3 alarms called Ia max, Ib max and Ic max, each alarm have to work in relationship with 3 contacts of the M6C.
The power shedding feature is not affected if you install a LT Off Rating Plug
發佈於: 施耐德電機Taiwan