How can I ensure that my HMISCU or XBTGC HMI Combo Controller starts in Run mode after a power cycle?
Issue
If I have downloaded a project from Vijeo Designer via File System USB memory stick to an HMISCU or XBTGC, the PLC does not start in RUN in subsequent power cycles.
How can I ensure that the PLC starts in RUN after power cycles when I download with this method?

Product Line
EcoStruxure Machine Expert v1.1+ / SoMachine v3.1 and higher
Harmony HMISCU and XBTGC

Environment
PLC Logic Builder and Vijeo Designer HMI configuration software in Windows

Cause
The flag for startup in the XBTGC and HMISCU is managed by a configuration file in their file system which can only be set with a cable (Ethernet or USB) download.
This flag is not settable using USB memory stick File System method of download.

The configuration flag is only set when these 3 conditions are met with a Cable-method download:
1) The download method is from the Online -> Multiple Download window
2) The "Start all applications after download or online change." checkbox is activated with a tick mark
3) The "<name>: HMI Application" is activated with a tick mark
Multiple Download dialog

This is not possible from Vijeo Designer's File System download.

Resolution
The method to always have the PLC start in RUN mode, regardless of Download method is to make a configuration change in Vijeo Designer by way of creating an Action in Vijeo Designer to write a non-zero value to a Variable with System Property @prop:0 on startup in order to guarantee the PLC starts in RUN after each power cycle.

Follow these two steps below to achieve this:

1) Create a new external variable INT in Vijeo Designer and address it as @prop:0. In this example, the Variable is named "RunController"
Create External Variable with @prop:0 assigned to Device Address

2) Create an action to write a non-zero value to the variable on startup.
Create new Action
Choose Startup Event Trigger
Set 1 to RunController
Resulting Action in Global Actions



[Other Useful Properties]
Here is a list of all driver properties for the HMISCU and XBTGC series HMI combo controllers that can be used as an Integer variable in Vijeo Designer:

@prop:0
  • Read/Write access
  • Writing any non-zero value will put the controller application in RUN

@prop:1
  • Read/Write access
  • Writing any non-zero value will put the controller application in STOP

@prop:2
  • Read-Only access
  • This returns an integer that is associated with the state of the controller
    • 0 - N/A
    • 1 - Running
    • 2 - Stopped
    • 3 - Error
@prop:3
  • Read-Only access
  • This returns an integer that is associated with the Error state of the controller
    • 0 - No Errors
    • 1 - Error

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings