How to add a Lantronix UDS1100 Ethernet Gateway Site in PME

Issue
Unable to communicate to a Lantronix UDS1100 using the default Lantronix MSS 3001 port.

Product Line

Lantronix


Environment

Power Monitoring Expert 7.2

Power Monitoring Expert 8.x

Power Monitoring Expert 9.x

Power Monitoring Expert 2021

Power Monitoring Expert 2022

Power Monitoring Expert 2023

Power Monitoring Expert 2024


Cause
Different model numbers of the Lantronix devices use different ports for communication.
The Lantronix MSS devices use port 3001 for channel 1 and 3002 for channel 2.
Lantronix UDS, CoBox, XPress, and XPort use 10001 for channel 1 and 10002 for channel 2.

Resolution
When adding the Ethernet Gateway Site for the Lantronix UDS1100:
1.) Add the site in Management Console

a.) Select Sites
b.) Right click on the right field and select New/Ethernet Gateway Site
c.) Enter the IP address for the gateway
d.) For TCP/IP Port type 10001 (ignore the fact that this may not be available in the dropdown and just type the numbers)

Port information

2.) Login to the Lantronix Web page of the UDS1100 by entering the IP address on the web browser, it will ask for a username/password, you can ignore it and just click on login
3.) Configure the Protocol, local Port and Port Settings to match downstream serial device. Example is given below.
Local Port
Serial Settings

4.) Return to Management Console> Sites
5.) Right click you site created above and select Connect
6.) Click Stay Connected

The site should connect to the lantronix and then show Connected in Management Console

施耐德電機Taiwan

探索更多
產品:
探索更多
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings