How to Fix "No Target Alive Found" Output with SCADAPack Workbench CAM5 (SCADAPack E)

When trying to write a SCADAPack Workbench solution to a SCADAPack E via TCP/IP, you may receive the "No Target Alive Found" message in the output window.

Workbench EConfigurator

One possible way to fix this challenge is to ensure you have ISaGRAF/TCP enabled in the TCP properties of the SCADAPack E Configuration. Once you have enabled the ISaGRAF/TCP service and written the configuration to the SCADAPack E, restart the RTU and attempt to write the SCADAPack Workbench solution to the RTU.

If this does not resolve your challenge, please contact SupportRO@se.com for further assistance.