我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
Can the PT windings' polarities be swapped without affecting the measurements ?

Issue
Both the primary and the secondary PTs have been reversed for ease of installations in some cases as shown below.

Normal PT setup Both of PTs primary and secondary sides are reversed
Normal PT Setup Primary and Secondary PT's reversed

Product Line
All Powerlogic devices that need a set of PTs

Resolution
Swapping the polarity at both the primary and secondary sides of the PT as shown in above diagram cancels the effect - the signal will not be inverted and the meter should be able to monitor the system as designed.  However, if only one of the sides is swapped, the signal will be inverted and the meter might not read the correct voltage values.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings