我们今天能为您提供什么帮助?

Can the ATV21, ATV212, or S-Flex drives communicate using Ethernet IP protocol?

Issue:
ATV21, ATV212, S-Flex drives network connection using Ethernet IP Communication

Product Line:
Altivar 21 / ATV21
Altivar 212 / ATV212
S-Flex enclosed drives

Resolution:
No.  These drives do not have the capability to connect directly to an Ethernet IP network.  A gateway is required to convert Ethernet IP to a standard protocol supported by the drive, such as Modbus RTU.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

施耐德電機Taiwan

探索更多

需要協助?

產品選型工具

快速輕鬆地為您的應用找到合適的產品和附件。

取得報價

立即線上提交您的銷售需求,專業團隊將主動聯繫您。

購買地點

輕鬆在您所在地區找到最近的施耐德電機經銷商。

支援中心

在同一位置找到滿足您所有需求的支援資源。