我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
LTMR08MFM has Earth fault protection with internal and external CT option? What is the necessity of external CT, when earth fault protection is available with internal option?
Find in attachment extract from LTMR manual. It explains the brief information's about ground fault using internal or external CT.

The ground CBCT is optional, since the ground current protection using internal current transformers is also possible based on calculation of ground current igr = i1 + i2 +i3 (sum of actual values in each phase).

The internal ground current fault threshold is 50% FLCmin
For LTMR08 FLCmax = 8Amps and FLCmin=1/20*FLCmax (ie,0.4Amps)
Hence the minimum ground fault threshold(50% FLCmin) = 0.2Amps and the response time is 500ms.

2. For the earth fault protection is with external CBCT is having minimum detected current 20mA and the response time is 100ms. Hence it indicates that the ground current protection with external CT is more accurate and faster than internal calculation.

Important : The ground fault protection in LTMR is meant only of equipment protection, for human protection the you need to use dedicated earth fault or earth leakage relays like Vigirex etc.

施耐德電機Taiwan

附件
LTMR - Ground fault protection.pdf [139.95 KB]
探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings