我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
What are the possible causes of motor choke over heating problem with ATV61/ATV71 drive?

- It is mentioned in the catalog that " Choke performance is ensured by not exceeding the cable lengths stated in catalog. For an application with several motors connected in parallel, the cable length must include all cabling. If a cable longer than that recommended is used, the motor chokes may overheat".

- For example, ATV61HD15N4 drive with VW3A5103 can be used up to 200 meters of cable length only. If the motor cable length is more than 200 meter, there may be possibility of the choke to get over heat. So you can use the choke reference VW3A5104, which can allow cable length up to 300 meter and this may solve the over heating problem.

- In many of installations, the armored cable are not considered as shielded cable, hence it may cause over heating of the choke. If armored cable is used, it is necessary to limit the cable length suitable for shielded cable.

- Requirement of ventilation is based on the ambient temperature. You should do the needful to maintain the ambient  temperature with in 50 degree C around the choke (inside the panel).

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings