In Vijeo Designer, how do we record the date and time to a variable when a button is pressed?
Issue:
How to record a timestamp to a variable when a button is pressed?

Product Line:
Vijeo Designer (all versions)

Resolution:
To record the date and time when a button is pressed, you will need to create a script in that button that copies the system variables _Hours, _Minutes, _Seconds, _Year2, _Month, _Day to a string variable for time and a string variable for date.

Please see the example script below:

//-------------------------------------
//Script Created: Jan 25, 2016
//
// Description:
//
//-------------------------------------

// Replace this line with your script
String YearYY = _Year2.getStringValue();
String MonthMM = _Month.getStringValue();
String DayDD = _Day.getStringValue();

if(_Month.getIntValue() < 10)
{
MonthMM = "0" + _Month.getStringValue();
}

if(_Day.getIntValue() < 10)
{
DayDD = "0" + _Day.getStringValue();
}


DateString.write(YearYY + "/" + MonthMM + "/" + DayDD);

String HoursHH = _Hour.getStringValue();
String MinutesMM = _Minutes.getStringValue();
String SecondsSS = _Seconds.getStringValue();

if(_Seconds.getIntValue() < 10)
{
SecondsSS = "0" + _Seconds.getStringValue();
}


if(_Hour.getIntValue() > 11)
{
temp.write(_Hour.getIntValue() - 12);
HoursHH = temp.getStringValue();
TimeString.write(HoursHH + ":" + MinutesMM + ":" + SecondsSS + " pm");
}
else
{
TimeString.write(HoursHH + ":" + MinutesMM + ":" + SecondsSS + " am");
}




施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings