The customer has lost the HTTP password of BMXNOR0200 module, how to retrieve this password

Issue : Customer has forgot the HTTP password for BMXNOR0200 module

Product line : Valid for BMXNOR0200 FW V1.7IR10

Environment : Unity Pro XL  V12 on Windows 7 Pro.

Resolution : The password can be retrieved by opening a FTP connection with the module.
Use Filezilla client in your PC to connect. Contact your local CCC to get credentials for FTP connection.

Look for the Userlist.dat in the web folder.
/SDCA/Web

Delete this file to move back to old default username and password which is USER in both cases.