我們的品牌

Impact-Company-Logo-English Black-01-177x54

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
How to determine which method to use for importing a third party manufacture eds file, if the hardware type is not known.
Issue
How to determine which method to use for importing a third party manufacture eds file, if the hardware type is not known.

Product Line
Unity

Environment
Windows 10

Resolution
The quickest way to determine which method to use for importing the eds file is view the '.eds' file with Notepad.

fdsf


If the device is described as an EthernetIP hardware the 'Add EDS to Library' selection in the DTM Browser must
be used to import the eds file.
  • Right click on the DTM hostname.
  • Click on 'Device menu'.
  • Click on 'Additional functions.
  • Click on 'Add EDS to library.
serfrf
  • Click on 'Next'.
wefr
  • Click on 'Add files'.
  • Click on 'Browse' and locate the edds file.
  • Click on 'Next'.
fewf


The 'DTM Catalog 'Update' button accessed from within Unity must be used. to update the hardware catalog.
  • Click on 'Tools\Hardare Catalog' to open the 'Hardware Catalog' window.
  • Click on 'DTM Catalog'.
  • Click on 'Update'.
wfrf


If the device is not described, it is most likely a CANOpen type hardware. The 'Hardware Catalog Manager'
must be used to import he eds file.
erf

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings