How do we control the Security InActivity timeout with a variable in Vijeo Designer?
Issue:
How do we control the Security InActivity timeout with a variable in Vijeo Designer?

Product Line:
Vijeo Designer (all versions)

Resolution:
Often times, the built-in time settings for the InActivity timeout for the Vijeo Designer Security feature are insufficient. Sometimes we would like a smaller amount of time to elapse instead, rather than the 1 minute minimum that is offered. In order to have a customizable Auto Logout Threshold, we can make use of some basic tools in Vijeo Designer. Please follow the procedure below to build this function yourself.

01) Create a Project named AutoLogoutForSecurity
02) Create a Security Group
03) Create a User
04) Set Target Security to "Use Security"
05) Drag a Login Part on to the Screen
06) Create an INT Variable named "Timer"
07) Create an INT Variable  named "AutoLogoutThreshold". Set its initial value to 10 for 10 seconds
08) Draw Numeric Displays for both Variables with labels
09) Create an action with "Trigger Type" set to "Event" and "Trigger Event" set to "When Touch Panel"
10) Set the action's operation to reset "Timer" to 0
11) Create an action with Trigger Type set to "Periodic" and "Frequency" set to 1 second.
12) Set the action's operation to Decision.
13) Set the Condition to (Timer < AutoLogoutThreshold)
14) If the conditon is True, increment "Timer". If the conditon is False, Run the Script "Sys.logout();" and reset "Timer" to 0

This will result in a project that has the ability to change the InActivity timeout to any value from 0 to 63563 seconds.

施耐德電機Taiwan

探索更多
系列:
探索更多
系列:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings