我們的品牌

歡迎造訪施耐德電機全球網站

歡迎訪問我們的網站
		
我们今天能为您提供什么帮助?
ADVC Controller Test and Training Set does not show the correct series
Issue
When the test and training set (TTS) is connected to the ADVC Controller it is showing a U-Series Recloser instead of a N-Series Recloser.

Product Line
ADVC II, Recloser, U-Series, N-Series, and W-Series

Environment
Testing the Recloser settings.

Cause
The old calibration files took the form of the first Recloser series that the TTS connects to.  The series cannot be changed after that.

Resolution
In order to have the TTS have the ability to switch between series the calibration file needs to be N24-150s (24kV 150kV BIL 1A CT's).
Attached is the calibration file, instructions on how to check the calibration file and how to load the file, and application notes about the calibration file.

Note:  The firmware of the ADVC Controller firmware must be A45-11.01 or above.

施耐德電機Taiwan

附件
SN392796.zip [511 Bytes]
Schneider Reclosers ADVC Writing .cal file to TTS 1.0.pdf [300.92 KB]
Application Notes A45 multiple switch series TTS R03.pdf [24.63 KB]
探索更多
系列:
產品:
探索更多
系列:
產品:
  • 產品文檔
  • 軟體下載
  • 產品選型工具
  • 產品替代和替換
  • 幫助和聯絡中心
  • 尋找我們的辦公室
  • 取得報價
  • 施耐德電機社群
  • 人才招募
  • 公司簡介
  • 舉報不當行為
  • 無障礙
  • 新聞中心
  • 投資者
  • 專業洞察
  • 台灣施耐德電機學院
  • 綠色影響力落差調查
  • Schneider Go Green 2025
  • 隱私政策
  • Cookie通告
  • 使用條款
  • Change your cookie settings